Air Handling Units (AHU) chính Hãng Vertiv năm 2024
Mô tả
Liebert Air Handling Unit (AHU)
Giới thiệu Thiết bị xử lý không khí Liebert (AHU) – Vertiv giải pháp quản lý nhiệt cho các trung tâm dữ liệu lớn với công suất lớn hơn & hiệu suất tốt hơn
Liebert Chilled Water Air Handling Unit AHU
Modularity – Easy to move & Quick to Install
Liebert Air Handling Unit (AHU) units are customized to suit different room space and transportation.
Highly Eighly
– Mechanical PUE less than 1.2 as part of a system
– Use of EC fans for lower motor power usage
– Self-optimizing controls reduce over-cooling and under-cooling
– Uniform airflow and temperature across the supply air side
Greater Protection AHU
– Advanced monitoring and event notification
– Finely tuned & advanced controls for more consistent supply air temperature & eliminating hot spots through rack inlet temperature sensor
– Feasible with UPS to back up either to whole system or controller only
Lower Installation & Maintenance Costs
– Multiple section design minimizes shipping costs and speeds installation
– Less component to maintain and ease of access for better service and maintenance
Insight for Action AHU
– Simplified access to realtime data and trending
– Quick diagnostics of potential critical events
Cooling Capacity AHU
Customized design based on diffrent cooling load requirement, airflow and other specific customer requirements. It does not require unit knock down on site for transportation, better quality control & less components to maintain and service.
Liebert Air Handling Units (AHU) are best used with Liebert intelligent controllers, wired or wireless rack sensors, and a Liebert central optimizing system control to ensure that the entire data center system is optimized with the other components of the chilled water system. Liebert intelligent control algorithms continuously process readings from the rack inlet sensors to ensure optimal air flow through the system while supply air sensors are used to control the unit cooling capacity. Varies teamwork modes harmonize the operation of multiple air handling units to eliminate conflicts in temperature, airflow, and humidity.
Unit Model AHU | FA200HC | FA300HC | FA400HC | FA500HC |
Net sensible cooling capacity(kW) | 200 | 300 | 400 | 500 |
Sensible cooling ratio | 100% | 100% | 100% | 100% |
Unit airflow(m/h) | 46000 | 69000 | 92000 | 115000 |
ESP (Pa) | 100 | 100 | 100 | 100 |
Unit inlet air temperature ( C) | 38 | 38 | 38 | 38 |
Unit inlet air relative humidity (%) | 35% | 35% | 35% | 35% |
Supply air temperature ( C) | 25 | 25 | 25 | 25 |
Inlet water temperature ( C) | 15 | 15 | 15 | 15 |
Outlet water temperature | 22 | 22 | 22 | 22 |
Internal filter class | F6 | F6 | F6 | F6 |
Unit power input (kW) | 8.5 | 11.7 | 16.3 | 22.7 |
Unit fluid side pressure drop (kPa) | 20 | 20 | 30 | 50 |
Unit fluid flow (L/s) | 7.1 | 10.7 | 14.6 | 17.9 |
Unit width (mm)* | 2200 | 2800 | 3600 | 4000 |
Unit depth (mm) | 2200 | 2200 | 2200 | 2200 |
Unit height (mm) | 3400 | 3400 | 3400 | 3400 |
Hãy đặt nền móng cho sự hợp tác bằng cách gọi cho tôi
(Mr Hoàng) Hotline: 0374585868
Website:VOIMT.COM
Đánh giá
Chưa có đánh giá nào.