A 625kVA UPS is a high-capacity power backup system designed to provide reliable, continuous power to critical equipment during outages or fluctuations in the main power supply. The “kVA” rating refers to kilovolt-amperes, a measure of apparent power, which indicates the system’s capacity to handle loads. For a 625kVA UPS, this typically translates to supporting substantial power demands, often seen in data centers, industrial facilities, or large commercial buildings.
These systems usually include battery backup to maintain power during short-term outages and can be paired with generators for extended downtime. Depending on the design, a 625kVA UPS might deliver around 500-625kW of real power (assuming a power factor of 0.8 to 1.0, common in such systems), though this varies by manufacturer and model. Features often include surge protection, voltage regulation, and scalability options, such as modular designs that allow expansion.
625KVA Liebert EXL S1 delivers an outstanding double conversion efficiency of up to 97%, which further increases up to 99% with the dynamic online mode, consequently reducing operating costs and energy dissipation (kW) to a minimum. This significantly minimizes the consumption of the cooling system, providing an overall TCO reduction and rapid payback time.
Furthermore, through its intelligent ECO mode efficiency and the intelligent paralleling feature Liebert EXL S1 can optimize efficiency even at partial load achieving additional superior cost savings.
Dynamic Online mode: No more availability tradeoff with efficiency
Dynamic Online mode is the latest high efficiency mode of operation offered by Vertiv, developed for those that do not want to trade off any level of availability for incremental gains in efficiency.
Dynamic Online mode enables operating efficiency up to 99% without sacrificing availability. In fact, while in this mode, the inverter can instantaneously assume the load and maintain the output voltage within the IEC 62040 Class 1 specification, thus offering the same level of availability typically achieved in a double conversion operating mode.
Dynamic Online mode is therefore able to combine the superior availability of a double conversion operating mode with the excellent energy cost savings of a high efficiency mode for a reduced total cost of ownership.

Technical Specifications |
625 |
UPS Rating (kVA) | 625KVA |
Output Active Power at 104°F (40°C) (kW) | 625KW |
Input AC Parameters | |
Input Voltage to Rectifier/ Bypass (VAC) | 480, 3-phase, 3-wire |
Permissible Input Voltage Range | +10%, -15% |
Input Frequency (Hz) | 60 ± 5Hz |
Input Power Factor | ≥ 0.99 |
Input Current Distortion (THDi) at Nominal Voltage at Full Load (%) | ≤ 3.0 |
Power Walk-in (seconds) | 1 to 300 (selectable in 1 second increments) |
Battery & DC Parameters Battery Type |
Lithium ion, VRLA (Valve Regulated Lead Acid), VLA (Vented Lead Acid) |
Nominal Battery Bus (VDC) / Battery Float Voltage (VDC) | 480 / 540 |
DC Ripple at Float Voltage | < 1.0% (RMS value) < 3.4% Vpp |
Temperature Compensated Battery Charging | Standard with Vertiv™ Battery Cabinets |
Output Parameters |
|
Load Power Factor Supported (Without Derating) | 0.7 Leading to 0.4 Lagging |
Output Voltage (VAC) | 480, 3-phase, 3-wire |
Output Voltage Regulation (%) / Output Voltage Regulation< 1.0 (3-phase RMS average) / < 2.0 (3-phase RMS average) (50% Unbalanced Load) (%) | |
Output Frequency (Hz) | 60 ± 0.1% |
Output THD at Nominal Voltage (Linear Load) (%) | ± 1.5 (RMS value) |
Output THD at Nominal Voltage including a 100kVA Non Linear Load per IEC 6204-3 (%) | ± 5.0 (RMS value) |
Translent Recovery 100% Load Step / 50% Load Step / Loss of/Return to AC Input Power | ±4% / ±2% / ±2% (RMS average for one cycle) |
Voltage Displacement (Balance Loads) / Voltage Displacement (50% Balance Loads) | 120 deg ±1 deg / 120 deg ±2 deg |
Overload at Nominal Voltage and 77°F (25°C) | 110% continuously, 125% for 10 minutes, 150% for 60 seconds, 200% for 200 miliseconds |
Physical Characteristics | |
Dimensions with Standard I/O Cabinet, W x D x H | 78.8 in x 36.0 in x 79.1 in |
Dimensions with BFD or Sharing Inductor I/O Cabinet, W x D X H | 109.4 in x 36.0 in x 79.1 in |
Weight with Standard I/O Cabinet, Unpackaged | 3508 lbs |
Weight with BFD or Sharing Inductor I/O Cabinet, Unpackaged | 5665 lbs (max) |
Color | Black, RAL 7021 |
Protection Class, UPS Enclosure | NEMA 1, IP 20 (with and without front door open) |
Environmental | |
Operating Temperature | 32°F to 104°F (0°C to 40°C) |
Relative Humidity | 0% to 95%, non-condensing |
Operating Altitude | Up to 3300 ft (1000 m) without derating |
Communications | |
Options | 2 Liebert Intellislots |
Card Compatibility | IS-UNITY-DP, IS-485EXI |
Protocols Available | MODBUS-IP, MODBUS-485, BACNET-IP, BACNET-MSTP, SNMP, HTTP, LIFE™ Services |
Standards | |
Transportation / Safety | ISTA Procedure 3B / UL 1778 5th Edition; CSA 22.2 NO 107.3 |
EMI / Surge | IEC 62040-2; FCC Part 15, Class A / ANSI C624.41, Category B3 |
Seismic | IBC 2015, CBC 2016, ASCE, OSHPD |

Liebert EXL S1 features a transformer- free design with full IGBT three-level double conversion technology, providing extraordinary savings on installation and running costs, while at the same time delivering first class load protection.
Liebert EXL S1 also features a full IGBT three-level rectifier allowing for electrical infrastructure cost saving, reducing the size of gensets, circuit protection, cabling and transformers.
Flexibility and Compatibility UPS 625KVA
Liebert EXL S1 can be fully adapted to meet diverse system requirements in terms of power capacity and redundancy allowing for different system designs, thus ensuring maximum flexibility:
– Output Power Factor up to 1
– No power derating from 0.4 lagging to 0.7 leading
– Optimum space/power ratio