625KVA Liebert EXL S1 delivers an outstanding double conversion efficiency of up to 97%, which further increases up to 99% with the dynamic online mode, consequently reducing operating costs and energy dissipation (kW) to a minimum. This significantly minimizes the consumption of the cooling system, providing an overall TCO reduction and rapid payback time.

Furthermore, through its intelligent ECO mode efficiency and the intelligent paralleling feature Liebert EXL S1 can optimize efficiency even at partial load achieving additional superior cost savings.
Dynamic Online mode: No more availability tradeoff with efficiency
Dynamic Online mode is the latest high efficiency mode of operation offered by Vertiv, developed for those that do not want to trade off any level of availability for incremental gains in efficiency.

Dynamic Online mode enables operating efficiency up to 99% without sacrificing availability. In fact, while in this mode, the inverter can instantaneously assume the load and maintain the output voltage within the IEC 62040 Class 1 specification, thus offering the same level of availability typically achieved in a double conversion operating mode.

Dynamic Online mode is therefore able to combine the superior availability of a double conversion operating mode with the excellent energy cost savings of a high efficiency mode for a reduced total cost of ownership.

EXL S1 625KVA
EXL S1 625KVA

 

Technical Specifications

625
UPS Rating (kVA) 625KVA
Output Active Power at 104°F (40°C) (kW) 625KW
Input AC Parameters
Input Voltage to Rectifier/ Bypass (VAC) 480, 3-phase, 3-wire
Permissible Input Voltage Range +10%, -15%
Input Frequency (Hz) 60 ± 5Hz
Input Power Factor  ≥ 0.99
Input Current Distortion (THDi) at Nominal Voltage at Full Load (%) ≤ 3.0
Power Walk-in (seconds)  1 to 300 (selectable in 1 second increments)
Battery & DC Parameters
Battery Type
 Lithium ion, VRLA (Valve Regulated Lead Acid), VLA (Vented Lead Acid)
Nominal Battery Bus (VDC) / Battery Float Voltage (VDC) 480 / 540
DC Ripple at Float Voltage  < 1.0% (RMS value) < 3.4% Vpp
Temperature Compensated Battery Charging  Standard with Vertiv™ Battery Cabinets

Output Parameters

Load Power Factor Supported (Without Derating) 0.7 Leading to 0.4 Lagging
Output Voltage (VAC) 480, 3-phase, 3-wire
Output Voltage Regulation (%) / Output Voltage Regulation< 1.0 (3-phase RMS average) / < 2.0 (3-phase RMS average) (50% Unbalanced Load) (%)
Output Frequency (Hz)  60 ± 0.1%
Output THD at Nominal Voltage (Linear Load) (%) ± 1.5 (RMS value)
Output THD at Nominal Voltage including a 100kVA Non Linear Load per IEC 6204-3 (%) ± 5.0 (RMS value)
Translent Recovery 100% Load Step / 50% Load Step / Loss of/Return to AC Input Power ±4% / ±2% / ±2% (RMS average for one cycle)
Voltage Displacement (Balance Loads) / Voltage Displacement (50% Balance Loads) 120 deg ±1 deg / 120 deg ±2 deg
Overload at Nominal Voltage and 77°F (25°C) 110% continuously, 125% for 10 minutes, 150% for 60 seconds, 200% for 200 miliseconds
Physical Characteristics
Dimensions with Standard I/O Cabinet, W x D x H 78.8 in x 36.0 in x 79.1 in
Dimensions with BFD or Sharing Inductor I/O Cabinet, W x D X H 109.4 in x 36.0 in x 79.1 in
Weight with Standard I/O Cabinet, Unpackaged 3508 lbs
Weight with BFD or Sharing Inductor I/O Cabinet, Unpackaged 5665 lbs (max)
Color  Black, RAL 7021
Protection Class, UPS Enclosure NEMA 1, IP 20 (with and without front door open)
Environmental
Operating Temperature 32°F to 104°F (0°C to 40°C)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude  Up to 3300 ft (1000 m) without derating
Communications
Options 2 Liebert Intellislots
Card Compatibility IS-UNITY-DP, IS-485EXI
Protocols Available MODBUS-IP, MODBUS-485, BACNET-IP, BACNET-MSTP, SNMP, HTTP, LIFE™ Services
Standards
Transportation / Safety ISTA Procedure 3B / UL 1778 5th Edition; CSA 22.2 NO 107.3
EMI / Surge IEC 62040-2; FCC Part 15, Class A / ANSI C624.41, Category B3
Seismic IBC 2015, CBC 2016, ASCE, OSHPD
625KVA
625KVA

Liebert EXL S1 features a transformer- free design with full IGBT three-level double conversion technology, providing extraordinary savings on installation and running costs, while at the same time delivering first class load protection.

Liebert EXL S1 also features a full IGBT three-level rectifier allowing for electrical infrastructure cost saving, reducing the size of gensets, circuit protection, cabling and transformers.

Flexibility and Compatibility UPS 625KVA

Liebert EXL S1 can be fully adapted to meet diverse system requirements in terms of power capacity and redundancy allowing for different system designs, thus ensuring maximum flexibility:
– Output Power Factor up to 1
– No power derating from 0.4 lagging to 0.7 leading
– Optimum space/power ratio

👉 https://voimt.com/Hãy đặt nền móng cho sự hợp tác bằng cách gọi cho tôi

(Mr Hoàng) Hotline: 0374585868

Website: VOIMT.COM

Đánh giá

Chưa có đánh giá nào.

Hãy là người đầu tiên nhận xét “625KVA UPS EXL S1 625KVA/625KW”

Email của bạn sẽ không được hiển thị công khai. Các trường bắt buộc được đánh dấu *

0374585868
0388454589