Rectifier Cabinet Netsure HDVC Hãng Vertiv
Mô tả
Rectifier Cabinet Features Netsure HDVC
• Power system controller monitors the rectifier cabinet status in real time; the 7-inch touch screen controls and manages the power system, and displays the system information.
• Supports remote monitoring and alarm function.
• High IP level without a bare live conductor.
• High level lightning protection at AC side with more than 40 kA capacity for discharging lightning surge current.
• Supports multiple cabinets connected in parallel for capacity expansion to 2250A.
• AC input of each rectifier supports independent MCB control.
• Supports integrated AC and DC distribution.
• Higher density: The footprint of a single cabinet 900 A system is only 600mm × 800mm.
• Full front access, easy front and rear maintenance; free cabling.
• Complies with China and EU environmental requirements
ITEM | DESCRIPTION |
AC Input | 300 A/3P × 3 terminals |
DC Output | Copper bus |
Rectifier Module | R400-15000e |
Controller Module | M822E |
AC SPD | 20 kA, up to 40 kA |
DC SPD | 10 kA |
REMARK | Three PCS 250 A/3P MCBs can be configured |
MODEL | DIMENSION (W × D × H ) IN MM | WEIGHT | REMARK |
NetSure HVT E02 CN1 | 600 × 800 × 2000 | ≤200 kg | Excluding rectifier |
NetSure HVT E02 CA1/C71 | 600 × 800 × 2200 | ≤200 kg | Excluding rectifier |
AC Cabinet Features
• Supports two AC inputs with mechanical interlock, and manual or auto switching function.
• Configured with an independent distribution controller unit that works independently to monitor the AC cabinet voltage, current, and branch status in real-time.
• Supports remote monitoring via Rs485 communication interface.
• Various kinds of AC information such as detected AC voltage, current, frequency, & lightning protection parameters are shown on the LCD screen.
• Supports top & bottom free cabling, full front access, flexible and convenient front & rear maintenance.
• Complies with IEC safety and lightning protection standards exhibits high safety.
• Level B or C lightning protection is available on the AC side.
• Complies with China and EU environment protection requirement.
Configuration |
|||
ITEM | PD380/630AFH | PD380/800AFA | PD380/1000AFH |
AC Input* | 3-phase 4-wire, 3-phase 5wire Two AC inputs, manual switching Input current: 630 A | 3-phase 4-wire, 3-phase 5-wire Two AC inputs, automatic switching Input current: 800 A | 3-phase 4-wire, 3-phase 5wire Two AC inputs, manual switching Input current: 1000 A |
AC Output | 3-phase 3 × 250 A (MCCB) 3-phase 1 × 63 A (MCB) 3-phase 1 × 32 A (MCB) Single-phase 3 × 32 A (MCB) Single-phase 3 × 20 A (MCB) |
3-phase 3 × 250 A (MCCB) | 3-phase 10 × 250 A (MCCB) 3-phase 1 × 63 A (MCB) 3-phase 3 × 32 A (MCB) |
MECHANICAL PARAMETERS | |||
Dimension (W × D × H) (mm) | 800 × 800 × 2000 | ||
Weight | ≤ 250 kg |
DC Cabinet, Secondary Distribution Cabinet
• Adaptive design that supports the installation of multiple types of protective devices.
• Intelligent design, with a separate distribution monitoring unit to realize the distributed power supply.
• LCD displays various kinds of information of DC cabinet and monitors the DC cabinet voltage, current, and branch status in real time.
• Supports remote monitoring & alarm function, with RS485 communication interface.
• Patented SPD module is configured on the DC side, which provides more than 10 kA surge protection capacity.
• Supports top & bottom free cabling, convenient and flexible front & rear operation and maintenance.
• High level security protection, More than IP20 protection level without a bare live conductor.
• Parallel expansion interface ensures reliable and safe capacity expansion.
• Complies with China and EU environment protection requirements.
Configuration Rectifier Cabinet Features
ITEM | PD400/630DF-2-Y3 | PD400/630DF-2-Y4 | PD400/1200DF-2-Y1 | PD400/1600DF-2-Y1 |
Type | Secondary distribution cabinet | Secondary distribution cabinet | DC cabinet | DC cabinet |
Battery Input | Fuse: 2 × 1250A | Fuse: 2 × 1600A | ||
DC Input | Fuse: 1 × 630A | Fuse: 1 × 630A | Parallel copper bus: 1250A | Parallel copper bus: 1600A |
DC Output | MCB: 56 × 32A/2P | Fuse: 10 × 250A | MCB: 8 × 250A/3P | Fuse: 5 × 630A; 5 x 250A |
Distribution Monitoring | Separate distribution monitoring | |||
Insulation Monitoring | Embedded | |||
DC SPD | Embedded | |||
Parallel Connection Interface | With parallel connection interface of copper bus | |||
MECHANICAL PARAMETERS | ||||
Dimension (W × D × H) (mm) |
800 × 600 × 2000 | 800 × 800 × 2000 | ||
Weight | ≤300 kg |
Configuration Netsure HDVC | ||
ITEM | PD400/250DF | PD400/400DF |
DC Input | Fuse: 2 × 250 A, or MCB: 2 × 250 A | MCB: 2 × 400 A |
DC Output (bi-polar MCB) | MCB: Route A, 24 × 32 A; Route B, 24 × 32 A | |
Branch Current Detection | Optional | |
Insulation Detector | Optional | |
MECHANICAL PARAMETERS | ||
Dimension (W × D × H) (mm) |
800 × 400 × 2000 | |
Weight | ≤200 kg |