Bộ lưu điện EXLS1 250KVA
Technical specifications bộ lưu điện EXLS1 250KVA |
|
UPS Rating (kVA) | 250KVA |
Output Active Power at 104°F (40°C) (kW) | 250KW |
Input AC Parameters Input Voltage to Rectifier/ Bypass (VAC) |
480, 3-phase, 3-wire |
Permissible Input Voltage Range | +10%, -15% |
Input Frequency (Hz) | 60 ± 5Hz |
Input Power Factor | ≥ 0.99 |
Input Current Distortion (THDi) at Nominal Voltage at Full Load (%) | ≤ 3.0 |
Power Walk-in (seconds) | 1 to 90 (selectable in 1 second increments) |
Battery & DC Parameters | |
Battery Type | Lithium ion, VRLA (Valve Regulated Lead Acid), VLA (Vented Lead Acid) |
Nominal Battery Bus (VDC) / Battery Float Voltage (VDC) | 480 / 540 |
DC Ripple at Float Voltage | < 1.0% (RMS value) < 3.4% Vpp |
Temperature Compensated Battery Charging | Standard with Vertiv Battery Cabinets |
Output Parameters |
|
Load Power Factor Supported (Without Derating) | 0.7 Leading to 0.4 Lagging |
Output Voltage (VAC) | 480, 3-phase, 3-wire |
Output Voltage Regulation (%) / Output Voltage Regulation | < 1.0 (3-phase RMS average) / < 2.0 (3-phase RMS average) (50% Unbalanced Load) (%) |
Output Frequency (Hz) | 60 ± 0.1% |
Output THD at Nominal Voltage (Linear Load) (%) | 1.5 (RMS value) |
Output THD at Nominal Voltage including a 100kVA Non Linear Load per IEC 6204-3 (%) | 5.0 (RMS value) |
Translent Recovery 100% Load Step / 50% Load Step / Loss of/ Return to AC Input Power | ±4% / ±2% / ±2% (RMS average for one cycle) |
Voltage Displacement (Balance Loads) / Voltage Displacement (50% Balance Loads) | 120 deg ±1 deg / 120 deg ±2 deg |
Overload at Nominal Voltage and 77°F (25°C) | 110% continuously, 125% for 10 minutes, 150% for 60 seconds, 200% for 200 miliseconds |
Physical Characteristics | |
Dimensions with Standard I/O Cabinet, W x D x H | 51.3 in x 36.0 in x 79.1 in |
Dimensions with BFD or Sharing Inductor I/O Cabinet, W x D X H | 63.2 in x 36.0 in x 79.1 in |
Weight with Standard I/O Cabinet, Unpackaged | 1869 lbs |
Weight with BFD or Sharing Inductor I/O Cabinet, Unpackaged | 2269 lbs (max) |
Color | Black, RAL 7021 |
Protection Class, UPS Enclosure | NEMA 1, IP 20 (with and without front door open) |
Environmental | |
Operating Temperature | 32°F to 104°F (0°C to 40°C) |
Relative Humidity | 0% to 95%, non-condensing |
Operating Altitude | Up to 3300 ft (1000 m) without derating |
Communications | |
Options | 2 Liebert Intellislots |
Card Compatibility | IS-UNITY-DP, IS-485EXI |
Protocols Available | MODBUS-IP, MODBUS-485, BACNET-IP, BACNET-MSTP, SNMP, HTTP, LIFE Services |
Standards | |
Transportation / Safety | ISTA Procedure 3B / UL 1778 5th Edition; CSA 22.2 NO 107.3 |
EMI / Surge | IEC 62040-2; FCC Part 15, Class A / ANSI C624.41, Category B3 |
Seismic | IBC 2015, CBC 2016, ASCE, OSHPD |
Standard Features
– Redundant DC variable speed fans
– Advanced compact power core
– Transformer-free design
– Up to 99% efficient
– Unity/Symmetrical power factor
– 100kA short circuit withstand rating
– Advanced status-at-a-glance touchscreen control panel
– Lithium-ion battery compatible
– Parallel up to 8 units
– Top and bottom entry cable access
– Front and top only service access
– Intelligent paralleling mode
– Parallel UPS system control and monitoring from a single touchscreen control panel
– Vertiv LIFE Services Remote
Diagnostic and Preventive Monitoring
Optional Features
– Dynamic Online (VI) mode
– Single or dual input
– DC battery ground fault detection
– Distributed paralleling
– Seismic anchoring kit
– Load bus synchronization
– Backfeed disconnect
– Bypass current sharing inductors
– Emergency Power Off
– Unity communications card allowing dual simultaneous protocols
– FCC Part 15 compliance